Certifying MPO Singlemode links with the CertiFiber Pro

This article describes a method for certifying Single Mode links with 8, 12 and 24 fiber pinned or unpinned MPO connectors at each end using the CertiFiber Pro.

Since this method requires the use of break out cables or cassettes (LC to unpinned MPO), the user needs to understand the desired polarity for their installation. L’utilisation de MultiFiber Pro  permettra une certification plus rapide. De plus, le MultiFiber Pro rapportera automatiquement la polarité.

Vous aurez besoin de :

  • CFP2-100-S or CFP2-100-Q Fluke Networks Certifiber Single Mode or Quad
  • SRC-9-SCLCAPCKIT Quantity 1 – Test reference cords for Single Mode LC/APC connectors
  • LCAPC to LCAPC reference grade patch cord Quantity 2 – no Fluke Networks part number
  • Duplex LC bulkhead adapters (Singlemode) Quantity 4
  • Uninned MPO to LC break out cable SBKC-MPOAPCU-LCAP Quantity 2 - from the cabling vendor you are testing
    • Alternatively, you can use a break out cable with gender changing connectors and test either pinned or unpinned links
    • Alternatively, you can use an MPO/MTP cassette (which is a break out cable in a small box)


​Additionally, inspection is critical for this method to work. Sans inspection, vous pourriez vous retrouver avec des résultats pessimistes. L’inspection inclut les extrémités des connecteurs MPO autant que celles des connecteurs LC. Les embouts des adaptateurs MPO sont disponibles pour le FiberInspector FI-1000 USB qui se raccorde à votre Versiv. Or you may use FI-3000 for MPO endface inspection. Don’t forget a cleaning kit.

  • FI1000 -- Inspection Camera
  • FI1000-1.25APC-TIP – LC APC patch cord inspection tip
  • FI1000-LCAPC-TIP – LC APC inspection tip for camera (Optional as needed)
  • FI1000-MPOAPC-XY – MPO Inspection tip for camera
  • Or Use FI-3000 for MPO Inspection
  • QuickClean-MPO-1P – MPO Cleaner
  • QuickClean-1.25-1P – LC Cleaner


     


​​

  1. Demandez à votre fournisseur/consultant en câblage ses limites de test. Here we shall use TIA-568.3-D-1 Multimode with a 3 Jumper Reference. You may have been told; "Never carry out a 2 or 3 Jumper Reference for link testing.”   
    However, for testing cables with a connector you don’t have on your power meter, like an MPO or an MTRJ, a 3 Jumper Reference is required.
  2. First, we are going to set up to do a 1 jumper reference, this will allow us to use the Set Ref Wizard.


     
  3. Inspect all cords before connecting them. Clean if necessary. Inspect again after you clean before connecting them.
  4. Insert the SC to LC APC TRCs into the output ports of the main and remote units.
  5. Connect the Versiv Main and Remote units together.




 

  1. From the HOME screen, tap SET REF > RUN WIZARD > NEXT
    Connect the cables as shown in the diagram and SET REFERENCE.
  2. Follow the step in the Wizard to set the reference and Verify the Test Reference Cords (TRC). Be sure that you have a loss value with the TRC of less than 0,25 dB. When following the Wizard, the TRC verification will be automatically saved.When you finish the wizard, press HOME.

  3. Go back into the test set up and select a 3 jumper reference. You will need to count the total number of connections that you have in your link including the test cords. Since we are going to ‘reference out’ the LC connections to the fanout cables, these two connectors will appear ‘outside the box’ on the setup screen.


     


 

  1. Now that you have the correct connector count for the loss budget calculation, return to the HOME screen and go to SET REF. With a 3 jumper reference selected, the SET REF Wizard will start with a 2 jumper reference that we have currently set up. Follow the steps in the Wizard to set the reference and to verify the 3rd jumper TRC.


     
  2. Make sure that you have a loss value of less than 0,25 dB for the TRC verification. The tester will warn you if you do not. If you do not, inspect and clean the connectors as needed and re-verify the TRC until you get less than 0,25 dB. This is important, and we will look for this in the test results to assure you are testing correctly. When you run the Wizard for TRC verification, it saves the result of that test along with your other test results.
  3. Remove the third jumper, the one in the middle. Inspect the LC connectors of the MPO fan out cable and attach the MPO fan out, or MPO/LC cassette, to both ends.


     
  4. Inspect the MPO/MTP connectors and clean if necessary. Now connect the MPO trunk cable to be tested.
  5. Test the LC connectors on both ends and go through the connectors. Depending on the polarity of the MPO trunk, you may need to switch the position of the Test Reference Cords.  
     

Informations complémentaires

  • Essayez en premier lieu dans vos locaux afin de vous assurer que vous êtes à l’aise avec la procédure.
  • Assurez-vous que vous avez disposé les câbles lors de la définition d’une référence, évitez les boucles dans le câble.
  • Re-verify the test reference cords every 500 tests, per steps 5-7 above. Les résultats de la revérification doivent être enregistrés.
  • Les connecteurs LC sont généralement homologués pour 500 insertions.
  • Les connecteurs sont homologués pour 500 et 1000 insertions - vérifiez auprès de votre fournisseur. (Il est supposé que vous vous connectez à l’aide de connecteurs propres)

 

Auteur : Jim Davis

Date de création : 2019-3-21

Date de la dernière modification : 2019-3-21

 
 
 
 